Cold winter air holds very little moisture. Once heated indoors, its relative humidity (RH) can fall below 20%, well under the recommended 40–60%. That causes discomfort and static, can help some viruses survive, and damages materials and processes. A well-specified, well-maintained humidification system fixes it.
Why is humidity so low in winter?
Relative humidity is how much water vapour the air holds compared with the most it could hold at that temperature. Heating air raises that maximum but adds no water, so RH falls.
When air handling units bring in damp outdoor air and heat it to 21°C, the result is very dry indoor air:
| Outdoor air | RH once heated to 21°C |
| −5°C at 90% RH | about 15% |
| 0°C at 85% RH | about 21% |
| 5°C at 80% RH | about 28% |
| 10°C at 75% RH | about 37% |
What is the ideal indoor humidity in winter?
For most buildings, 40–60% RH. That is high enough to prevent dryness and static, and low enough to avoid condensation and mould. Processes such as printing, timber, electronics and archives may need their own specified range.
How does low humidity affect health and comfort?
Low humidity is hard to feel directly, so people usually notice the symptoms first:
- Dry, itchy skin and cracked lips
- Dry eyes, especially for contact lens wearers
- Sore throats, nosebleeds and headaches
- Static shocks
Research also links dry air to the spread of winter viruses. A 2019 study found that mice kept at 10–20% RH had weaker airway defences against influenza than those at 50%. A 2013 study found that flu virus lost much more of its infectivity at 43% RH or above than at 23% or below.
How does low humidity affect manufacturing and materials?
Paper, timber and textiles lose moisture in dry air, so they shrink, curl or crack. Dry air also lets static build up. The result is downtime, waste and lower productivity:
| Sector | What low humidity causes |
| Printing and packaging | Paper curl, jams, misfeeds and static cling |
| Woodworking and furniture | Shrinkage, splitting and warping; open joints |
| Electronics and data centres | Electrostatic discharge (ESD) damaging components |
| Textiles | Fibre breakage and static on high-speed machinery |
| Museums and archives | Cracking and flaking of collections |
| Offices | Discomfort, static shocks and complaints |
How can you tell if humidity is too low?
Measure it with a calibrated hygrometer, a data logger or your building management system’s sensors. Readings consistently below 40% in the heating season mean you have a problem. Warning signs include frequent static shocks, staff complaining of dry eyes or sore throats, paper jams, cracking timber and higher winter waste.
How do you choose the right humidification system?
It depends on the building, the process and running costs. The two main families are:
| Type | How it works | Best for | Trade-off |
| Steam | Boils water (electric or gas) and injects steam | Precise control, hygiene-critical spaces | Higher energy use |
| Adiabatic | Evaporates cold water as a spray or through pads | Large spaces such as warehouses and print halls | Low energy; needs strict water hygiene |
Also consider where the unit goes (air handling unit or in the room), water treatment, compatibility with your building management system, and whole-life cost. Humidifiers are a recognised Legionella risk under HSE’s guidance on other risk systems, so they need a risk assessment and documented maintenance. A planned maintenance contract covers both.
Humidity Solutions’ engineers survey, design, install, commission and maintain the right system, so you have one point of contact for its whole life.
Get your humidity under control this winter
If your building is running dry, or you’re not sure, our engineers can measure your current conditions and recommend the right solution. Book a site survey or call us on 01372 571 200.
Frequently asked questions
Heating cold outdoor air raises its capacity to hold water but adds none, so relative humidity falls, often below 20%.
40–60% RH for comfort; some processes need a specific range.
Yes. Dry air lets static build up, causing shocks, sticking materials and damage to electronics.
Yes. Regular servicing keeps them efficient, and HSE guidance requires their Legionella risk to be assessed and managed.